The accessible urinal is required to have a 30 x 48 760 mm x 1220 mm clear floor or ground space positioned for forward approach.
Does an non accessible floor need accessible toilet.
Where technical infeasibility is encountered compliance is still required to the maximum extent feasible.
Image caption a changing places toilet allows for more space than a standard accessible toilet but at present are only a building regulations recommendation rather than compulsory.
When it is technically infeasible to make existing men s and women s rooms comply an accessible unisex toilet room can be provided instead if it is in the same area and on the same floor as the existing toilet rooms 213 2 ex.
Class 10a at least 1 accessible unisex sanitary facility at each bank of sanitary facilities for males and females.
Essentially wherever toilets are provided in buildings that are required to be accessible in most cases at least 1 accessible unisex sanitary facility must be provided.
Refer to figure e.
The unisex facility shall be located on the same floor and in the same area as the existing facilities.
Refer to figure a.
Refer to figure b.
Where urinals are placed in a alcove deeper than 24 610 mm then the alcove must be 36 min 915 mm wide.
The door swing is allowed to overlap the clearance for a water closet and a lavatory in a toilet room as long as there is a 30 760 mm x 48 1220 mm clear floor space beyond the arc of the door.
213 2 toilet rooms and bathing rooms.